✨ New Arrivals Just Dropped!Explore
Polypipe Zonal Regulation Unit 2/3 Circuit ZRU Complete with Manifold
HomeStore

Polypipe Zonal Regulation Unit 2/3 Circuit ZRU Complete with Manifold

Polypipe Zonal Regulation Unit 2/3 Circuit ZRU Complete with Manifold

Underfloor Heating Single Room / Extension Up to 30 m² 2 or 3 Circuits Built-in Pump & Mixing Valve Domestic & Commercial Polypipe UFH

The Polypipe Zonal Regulation Unit (ZRU) is a complete, self-contained underfloor heating control unit that allows a single room or extension of up to 30 m² to be connected to an existing wet central heating system — with no costly hydraulic alterations, no new wiring centres, and no changes to the existing boiler or radiator circuits. It bridges the temperature gap between a radiator system (typically 70–80°C flow) and the lower temperatures required for underfloor heating (30–55°C) using a built-in thermostatic blending valve. A dedicated pump within the unit provides the correct flow rate for the UFH loops independently of the existing system pump. The PB970028 variant includes a built-in 2-circuit manifold as standard; a third circuit can be formed by adding two 15mm spigot elbows and two 15mm tees (sold separately).

  • Connects single rooms or extensions up to 30 m² to any existing 2-pipe wet heating system
  • No hydraulic or electrical alterations to the existing heating system required
  • Built-in thermostatic blending valve blends flow water to the correct UFH temperature (30–60°C)
  • Dedicated integral pump boosts flow — UFH loops are not dependent on the existing system pump
  • Built-in pipe thermostat senses available heat — pump only runs when boiler water exceeds 45°C
  • Optional volt-free room thermostat or wireless sensor connection for precise air temperature control
  • 2-circuit manifold built in as standard — expandable to 3 circuits with standard 15mm fittings
  • Can operate the UFH zone independently of the rest of the heating system when used with a zone valve
  • Also suitable for low surface temperature (LST) radiator applications where water temperature control is needed
  • Wall-mounted in the heated room or positioned elsewhere in the property — fully flexible siting
  • Suitable for domestic and commercial buildings
  • Compatible with all Polypipe UFH systems: Overlay™, Overlay™ Lite, MHP, solid screeded floors, and more
Zonal Regulation Unit body (pump, blending valve, pipe stat)
2-circuit built-in manifold (flow & return)
Wiring module with terminal block
Wall fixing template & screws
Fixing plugs
Installation guide
ℹ️ 3rd circuit upgrade: To form a third heating circuit, add 2 × 15mm spigot elbows and 2 × 15mm tees to the ZRU manifold ports. These standard Polypipe PolyPlumb fittings are sold separately.

The ZRU forms a low-loss header between the existing heating circuit and the UFH loops, managing temperature and flow automatically. The six-step operational sequence is:

  1. Boiler fires: Heating water circulates from the boiler through the existing system pipework and enters the ZRU via the Heating Flow connection.
  2. Pipe thermostat activates: The built-in pipe thermostat senses that heating water is available (≥45°C) and sends a live signal to the ZRU pump.
  3. Room thermostat calls for heat: If a room thermostat is fitted and the room temperature is below setpoint, the pump starts and draws water into the UFH circuits.
  4. Thermostatic blending valve regulates temperature: A mixture of hot flow water and cooler UFH return water is blended to the correct underfloor temperature (adjustable 30–60°C) before being pumped into the loops.
  5. Room thermostat satisfied: When the room reaches setpoint, the thermostat breaks the signal to the pump — the UFH pump stops, but the existing heating system continues to run normally.
  6. Boiler shuts down: As the boiler switches off and main flow water cools below 45°C, the pipe thermostat breaks the pump signal and the ZRU goes to standby.
MPN / Product Code PB970028
Manufacturer Polypipe
Product Type Zonal Regulation Unit (ZRU) — 2/3 Circuit, complete with manifold
Max Room / Extension Area Up to 30 m²
Number of UFH Circuits 2 (built-in manifold); expandable to 3 with standard 15mm fittings
Flow Temperature Control Thermostatic blending valve — adjustable 30°C to 60°C
Minimum Boiler Water Temperature to Activate 45°C (pipe thermostat make point)
Pipe Thermostat: Make / Break Makes at 40°C / Breaks at 32°C
Electrical Supply 240V AC, 3A fused spur
Room Thermostat Connection Volt-free contact (battery-operated or wired thermostat); remove link on wiring block when thermostat fitted
Pipework Connections 15mm compression — Heating Flow, Heating Return, UFH Flow(s), UFH Return(s)
Minimum Pipe Size to ZRU 15mm (do not connect from any pipe smaller than 15mm)
Preferred System Connection Main 22mm flow and return distribution pipework of a 2-pipe system
Pressure Rating PN6
Max Ambient Temperature 60°C (at 95°C fluid temperature)
Mounting Wall-mounted — 100mm minimum from finished floor level
Mounting Clearance 80mm minimum wall clearance for mixing valve adjustment access
Application Domestic and commercial — all Polypipe UFH floor types
Compatible UFH Systems: Polypipe Overlay™ · Overlay™ Lite · MHP (Minimum Depth) · Solid screeded floor systems · Low surface temperature (LST) radiator applications
⚠️ Competent person required: All electrical connections must comply with the current edition of BS 7671 (IET Wiring Regulations). Electrical work must be carried out by, or inspected and tested by, a qualified electrician. Plumbing connections must comply with the Water Supply (Water Fittings) Regulations 1999. Always check boiler manufacturer guidance before installing a second pump on the system.
  1. Pre-fill UFH pipework: If the ZRU is to be installed after floor screed or coverings are laid, fill and pressure-test the UFH circuit beforehand. Temporarily cap the pipes and keep them full of water (under pressure where possible). Take precautions against freezing in cold conditions.
  2. Select mounting position: Ideally mount in the heated room at 100mm above finished floor level to allow pipe connections to exit the floor correctly. The ZRU can alternatively be positioned elsewhere in the property if more convenient. Ensure 80mm minimum clearance to the left of the unit for mixing valve access.
  3. Fix to wall (Step 1): Tape the supplied fixing template to the wall. Mark and drill fixing holes. Insert wall plugs and screw the ZRU body firmly to the wall. Do not over-tighten fixings.
  4. Connect heating pipework (Step 2): Connect the Heating Flow and Heating Return ports to the existing 2-pipe system via isolation valves. The preferred connection point is the main 22mm distribution pipework. Alternatively connect to the nearest existing radiator. Do not connect from any pipe smaller than 15mm.
  5. Connect UFH circuits (Step 3): Connect the underfloor heating flow and return loops to the ZRU manifold ports using isolation valves. For 2 circuits, use the built-in manifold ports. To add a 3rd circuit, fit 15mm spigot elbows to the underside exit points and use 15mm tees off the manifold. Blank off any unused ports with spigot blanking plugs. Use PolyPlumb elbow fittings to exit pipes from floor level; cover elbows in polystyrene before screeding to allow future access, or enclose within a PolyPlumb Junction Box.
  6. Wire electrical connections (Step 4): Connect 240V mains supply via a 3A fused spur to the ZRU wiring block as per the wiring diagram in the installation guide. If a room thermostat is being fitted, connect the volt-free contacts to the designated terminals and remove the shorting link from the wiring block. If no thermostat is fitted, leave the link in place — the ZRU will run purely on pipe thermostat control.
  7. Fill and commission: Fill the complete system (boiler, radiators, and UFH circuits) and bleed any air. Check all connections for leaks. Set the thermostatic blending valve to the desired UFH flow temperature (typically 35–50°C depending on floor construction). Fire the boiler and confirm the ZRU pump starts when flow temperature exceeds 45°C. Verify correct operation of the room thermostat (if fitted).
ℹ️ Solid floor timing note: For solid screeded floor installations, the thermal mass of the floor means slow response times. The timings of the existing central heating may need adjusting so the UFH circuit has sufficient warm-up time before occupancy. Low-mass systems (Overlay™, Overlay™ Lite, MHP) respond much faster and are generally compatible with existing boiler on/off timing.
💡 Independent zone operation: To operate the UFH room completely independently of the existing heating system (e.g. different schedule or setpoint), install a zone valve between the boiler/distribution pipework and the ZRU Heating Flow connection, controlled by a programmable room thermostat. Without this, the ZRU will only operate when the existing heating system is also running.
Can I add underfloor heating to just one room without changing my existing radiator system?
Yes — that is exactly what the ZRU is designed for. It connects a single room or extension to your existing radiator circuit without any modifications to the boiler, pump, or existing pipework. It has its own pump and mixing valve and manages the temperature conversion internally.
My existing system runs at around 75°C. Is that too hot for UFH?
Not with the ZRU. The built-in thermostatic blending valve reduces the flow temperature to between 30°C and 60°C before it reaches the UFH pipework. You set the blending valve to the appropriate temperature for your floor construction — typically 35–45°C for a screed floor and up to 50°C for a timber floor system.
Does the ZRU work if my boiler is a combi?
Yes, the ZRU is compatible with combi boilers. However, note that adding a second pump to the system can affect some boilers hydraulically — always check with the boiler manufacturer that a second pump is compatible before installation.
What happens if my boiler is off? Will the underfloor heating still work?
No — the ZRU only operates when the boiler is supplying heat. The pipe thermostat within the unit detects when flow water reaches 45°C and only then starts the UFH pump. If the boiler is off, the ZRU pump will not run. To allow the UFH to run independently on a separate schedule, a zone valve is needed (see installation note above).
How many circuits can the ZRU serve?
The PB970028 includes a built-in 2-circuit manifold, so it can serve two UFH loops directly out of the box. A third circuit can be added by fitting two 15mm spigot elbows and two 15mm tees to the manifold — standard PolyPlumb fittings available separately. For rooms over 30 m², Polypipe recommend connecting via a full multi-circuit manifold rather than a ZRU.
Do I need a room thermostat?
A room thermostat is optional. Without one, the ZRU operates purely on the pipe thermostat — running whenever the boiler is on and stopping when the boiler shuts down. Adding a volt-free room thermostat (battery-operated or wired) allows the room temperature to be set and maintained precisely, stopping the UFH pump once the room reaches temperature even if the boiler is still running. This is strongly recommended for energy efficiency and comfort.
Where should the ZRU be mounted?
Ideally on the wall of the room being heated, at 100mm above the finished floor level so that the UFH pipe connections exit from the floor cleanly beneath it. If this is not practical, it can be positioned elsewhere in the property — for example in a hallway cupboard — as long as the pipe stat will still accurately detect the system flow temperature.
What pipe size is required to connect the ZRU?
All connections to the ZRU are 15mm compression. The ZRU must not be connected to the existing system from a pipe smaller than 15mm. The preferred connection point is the main 22mm flow and return distribution pipework; the system can also be connected from the nearest radiator if more convenient.
Can the ZRU be used for low surface temperature (LST) radiators instead of UFH?
Yes. Because the ZRU thermostatically controls water temperature, it can also be used to supply low surface temperature radiators where the maximum surface temperature must be limited — for example in schools, care homes, or healthcare settings.
What floor types is the ZRU compatible with?
The ZRU is compatible with all Polypipe wet UFH systems: screeded solid floor systems, Overlay™ low-profile board systems, Overlay™ Lite, and MHP (Minimum Depth Panel) systems. For low-mass systems (Overlay™, Overlay™ Lite, MHP), the fast response means the ZRU works well with the existing boiler's on/off timer. For solid screeded floors, you may need to advance the existing heating start time to allow the floor mass to warm up in time.
$361.85

Original: $1,033.85

-65%
Polypipe Zonal Regulation Unit 2/3 Circuit ZRU Complete with Manifold

$1,033.85

$361.85

Polypipe Zonal Regulation Unit 2/3 Circuit ZRU Complete with Manifold

Underfloor Heating Single Room / Extension Up to 30 m² 2 or 3 Circuits Built-in Pump & Mixing Valve Domestic & Commercial Polypipe UFH

The Polypipe Zonal Regulation Unit (ZRU) is a complete, self-contained underfloor heating control unit that allows a single room or extension of up to 30 m² to be connected to an existing wet central heating system — with no costly hydraulic alterations, no new wiring centres, and no changes to the existing boiler or radiator circuits. It bridges the temperature gap between a radiator system (typically 70–80°C flow) and the lower temperatures required for underfloor heating (30–55°C) using a built-in thermostatic blending valve. A dedicated pump within the unit provides the correct flow rate for the UFH loops independently of the existing system pump. The PB970028 variant includes a built-in 2-circuit manifold as standard; a third circuit can be formed by adding two 15mm spigot elbows and two 15mm tees (sold separately).

  • Connects single rooms or extensions up to 30 m² to any existing 2-pipe wet heating system
  • No hydraulic or electrical alterations to the existing heating system required
  • Built-in thermostatic blending valve blends flow water to the correct UFH temperature (30–60°C)
  • Dedicated integral pump boosts flow — UFH loops are not dependent on the existing system pump
  • Built-in pipe thermostat senses available heat — pump only runs when boiler water exceeds 45°C
  • Optional volt-free room thermostat or wireless sensor connection for precise air temperature control
  • 2-circuit manifold built in as standard — expandable to 3 circuits with standard 15mm fittings
  • Can operate the UFH zone independently of the rest of the heating system when used with a zone valve
  • Also suitable for low surface temperature (LST) radiator applications where water temperature control is needed
  • Wall-mounted in the heated room or positioned elsewhere in the property — fully flexible siting
  • Suitable for domestic and commercial buildings
  • Compatible with all Polypipe UFH systems: Overlay™, Overlay™ Lite, MHP, solid screeded floors, and more
Zonal Regulation Unit body (pump, blending valve, pipe stat)
2-circuit built-in manifold (flow & return)
Wiring module with terminal block
Wall fixing template & screws
Fixing plugs
Installation guide
ℹ️ 3rd circuit upgrade: To form a third heating circuit, add 2 × 15mm spigot elbows and 2 × 15mm tees to the ZRU manifold ports. These standard Polypipe PolyPlumb fittings are sold separately.

The ZRU forms a low-loss header between the existing heating circuit and the UFH loops, managing temperature and flow automatically. The six-step operational sequence is:

  1. Boiler fires: Heating water circulates from the boiler through the existing system pipework and enters the ZRU via the Heating Flow connection.
  2. Pipe thermostat activates: The built-in pipe thermostat senses that heating water is available (≥45°C) and sends a live signal to the ZRU pump.
  3. Room thermostat calls for heat: If a room thermostat is fitted and the room temperature is below setpoint, the pump starts and draws water into the UFH circuits.
  4. Thermostatic blending valve regulates temperature: A mixture of hot flow water and cooler UFH return water is blended to the correct underfloor temperature (adjustable 30–60°C) before being pumped into the loops.
  5. Room thermostat satisfied: When the room reaches setpoint, the thermostat breaks the signal to the pump — the UFH pump stops, but the existing heating system continues to run normally.
  6. Boiler shuts down: As the boiler switches off and main flow water cools below 45°C, the pipe thermostat breaks the pump signal and the ZRU goes to standby.
MPN / Product Code PB970028
Manufacturer Polypipe
Product Type Zonal Regulation Unit (ZRU) — 2/3 Circuit, complete with manifold
Max Room / Extension Area Up to 30 m²
Number of UFH Circuits 2 (built-in manifold); expandable to 3 with standard 15mm fittings
Flow Temperature Control Thermostatic blending valve — adjustable 30°C to 60°C
Minimum Boiler Water Temperature to Activate 45°C (pipe thermostat make point)
Pipe Thermostat: Make / Break Makes at 40°C / Breaks at 32°C
Electrical Supply 240V AC, 3A fused spur
Room Thermostat Connection Volt-free contact (battery-operated or wired thermostat); remove link on wiring block when thermostat fitted
Pipework Connections 15mm compression — Heating Flow, Heating Return, UFH Flow(s), UFH Return(s)
Minimum Pipe Size to ZRU 15mm (do not connect from any pipe smaller than 15mm)
Preferred System Connection Main 22mm flow and return distribution pipework of a 2-pipe system
Pressure Rating PN6
Max Ambient Temperature 60°C (at 95°C fluid temperature)
Mounting Wall-mounted — 100mm minimum from finished floor level
Mounting Clearance 80mm minimum wall clearance for mixing valve adjustment access
Application Domestic and commercial — all Polypipe UFH floor types
Compatible UFH Systems: Polypipe Overlay™ · Overlay™ Lite · MHP (Minimum Depth) · Solid screeded floor systems · Low surface temperature (LST) radiator applications
⚠️ Competent person required: All electrical connections must comply with the current edition of BS 7671 (IET Wiring Regulations). Electrical work must be carried out by, or inspected and tested by, a qualified electrician. Plumbing connections must comply with the Water Supply (Water Fittings) Regulations 1999. Always check boiler manufacturer guidance before installing a second pump on the system.
  1. Pre-fill UFH pipework: If the ZRU is to be installed after floor screed or coverings are laid, fill and pressure-test the UFH circuit beforehand. Temporarily cap the pipes and keep them full of water (under pressure where possible). Take precautions against freezing in cold conditions.
  2. Select mounting position: Ideally mount in the heated room at 100mm above finished floor level to allow pipe connections to exit the floor correctly. The ZRU can alternatively be positioned elsewhere in the property if more convenient. Ensure 80mm minimum clearance to the left of the unit for mixing valve access.
  3. Fix to wall (Step 1): Tape the supplied fixing template to the wall. Mark and drill fixing holes. Insert wall plugs and screw the ZRU body firmly to the wall. Do not over-tighten fixings.
  4. Connect heating pipework (Step 2): Connect the Heating Flow and Heating Return ports to the existing 2-pipe system via isolation valves. The preferred connection point is the main 22mm distribution pipework. Alternatively connect to the nearest existing radiator. Do not connect from any pipe smaller than 15mm.
  5. Connect UFH circuits (Step 3): Connect the underfloor heating flow and return loops to the ZRU manifold ports using isolation valves. For 2 circuits, use the built-in manifold ports. To add a 3rd circuit, fit 15mm spigot elbows to the underside exit points and use 15mm tees off the manifold. Blank off any unused ports with spigot blanking plugs. Use PolyPlumb elbow fittings to exit pipes from floor level; cover elbows in polystyrene before screeding to allow future access, or enclose within a PolyPlumb Junction Box.
  6. Wire electrical connections (Step 4): Connect 240V mains supply via a 3A fused spur to the ZRU wiring block as per the wiring diagram in the installation guide. If a room thermostat is being fitted, connect the volt-free contacts to the designated terminals and remove the shorting link from the wiring block. If no thermostat is fitted, leave the link in place — the ZRU will run purely on pipe thermostat control.
  7. Fill and commission: Fill the complete system (boiler, radiators, and UFH circuits) and bleed any air. Check all connections for leaks. Set the thermostatic blending valve to the desired UFH flow temperature (typically 35–50°C depending on floor construction). Fire the boiler and confirm the ZRU pump starts when flow temperature exceeds 45°C. Verify correct operation of the room thermostat (if fitted).
ℹ️ Solid floor timing note: For solid screeded floor installations, the thermal mass of the floor means slow response times. The timings of the existing central heating may need adjusting so the UFH circuit has sufficient warm-up time before occupancy. Low-mass systems (Overlay™, Overlay™ Lite, MHP) respond much faster and are generally compatible with existing boiler on/off timing.
💡 Independent zone operation: To operate the UFH room completely independently of the existing heating system (e.g. different schedule or setpoint), install a zone valve between the boiler/distribution pipework and the ZRU Heating Flow connection, controlled by a programmable room thermostat. Without this, the ZRU will only operate when the existing heating system is also running.
Can I add underfloor heating to just one room without changing my existing radiator system?
Yes — that is exactly what the ZRU is designed for. It connects a single room or extension to your existing radiator circuit without any modifications to the boiler, pump, or existing pipework. It has its own pump and mixing valve and manages the temperature conversion internally.
My existing system runs at around 75°C. Is that too hot for UFH?
Not with the ZRU. The built-in thermostatic blending valve reduces the flow temperature to between 30°C and 60°C before it reaches the UFH pipework. You set the blending valve to the appropriate temperature for your floor construction — typically 35–45°C for a screed floor and up to 50°C for a timber floor system.
Does the ZRU work if my boiler is a combi?
Yes, the ZRU is compatible with combi boilers. However, note that adding a second pump to the system can affect some boilers hydraulically — always check with the boiler manufacturer that a second pump is compatible before installation.
What happens if my boiler is off? Will the underfloor heating still work?
No — the ZRU only operates when the boiler is supplying heat. The pipe thermostat within the unit detects when flow water reaches 45°C and only then starts the UFH pump. If the boiler is off, the ZRU pump will not run. To allow the UFH to run independently on a separate schedule, a zone valve is needed (see installation note above).
How many circuits can the ZRU serve?
The PB970028 includes a built-in 2-circuit manifold, so it can serve two UFH loops directly out of the box. A third circuit can be added by fitting two 15mm spigot elbows and two 15mm tees to the manifold — standard PolyPlumb fittings available separately. For rooms over 30 m², Polypipe recommend connecting via a full multi-circuit manifold rather than a ZRU.
Do I need a room thermostat?
A room thermostat is optional. Without one, the ZRU operates purely on the pipe thermostat — running whenever the boiler is on and stopping when the boiler shuts down. Adding a volt-free room thermostat (battery-operated or wired) allows the room temperature to be set and maintained precisely, stopping the UFH pump once the room reaches temperature even if the boiler is still running. This is strongly recommended for energy efficiency and comfort.
Where should the ZRU be mounted?
Ideally on the wall of the room being heated, at 100mm above the finished floor level so that the UFH pipe connections exit from the floor cleanly beneath it. If this is not practical, it can be positioned elsewhere in the property — for example in a hallway cupboard — as long as the pipe stat will still accurately detect the system flow temperature.
What pipe size is required to connect the ZRU?
All connections to the ZRU are 15mm compression. The ZRU must not be connected to the existing system from a pipe smaller than 15mm. The preferred connection point is the main 22mm flow and return distribution pipework; the system can also be connected from the nearest radiator if more convenient.
Can the ZRU be used for low surface temperature (LST) radiators instead of UFH?
Yes. Because the ZRU thermostatically controls water temperature, it can also be used to supply low surface temperature radiators where the maximum surface temperature must be limited — for example in schools, care homes, or healthcare settings.
What floor types is the ZRU compatible with?
The ZRU is compatible with all Polypipe wet UFH systems: screeded solid floor systems, Overlay™ low-profile board systems, Overlay™ Lite, and MHP (Minimum Depth Panel) systems. For low-mass systems (Overlay™, Overlay™ Lite, MHP), the fast response means the ZRU works well with the existing boiler's on/off timer. For solid screeded floors, you may need to advance the existing heating start time to allow the floor mass to warm up in time.

Product Information

Shipping & Returns

Description

Underfloor Heating Single Room / Extension Up to 30 m² 2 or 3 Circuits Built-in Pump & Mixing Valve Domestic & Commercial Polypipe UFH

The Polypipe Zonal Regulation Unit (ZRU) is a complete, self-contained underfloor heating control unit that allows a single room or extension of up to 30 m² to be connected to an existing wet central heating system — with no costly hydraulic alterations, no new wiring centres, and no changes to the existing boiler or radiator circuits. It bridges the temperature gap between a radiator system (typically 70–80°C flow) and the lower temperatures required for underfloor heating (30–55°C) using a built-in thermostatic blending valve. A dedicated pump within the unit provides the correct flow rate for the UFH loops independently of the existing system pump. The PB970028 variant includes a built-in 2-circuit manifold as standard; a third circuit can be formed by adding two 15mm spigot elbows and two 15mm tees (sold separately).

  • Connects single rooms or extensions up to 30 m² to any existing 2-pipe wet heating system
  • No hydraulic or electrical alterations to the existing heating system required
  • Built-in thermostatic blending valve blends flow water to the correct UFH temperature (30–60°C)
  • Dedicated integral pump boosts flow — UFH loops are not dependent on the existing system pump
  • Built-in pipe thermostat senses available heat — pump only runs when boiler water exceeds 45°C
  • Optional volt-free room thermostat or wireless sensor connection for precise air temperature control
  • 2-circuit manifold built in as standard — expandable to 3 circuits with standard 15mm fittings
  • Can operate the UFH zone independently of the rest of the heating system when used with a zone valve
  • Also suitable for low surface temperature (LST) radiator applications where water temperature control is needed
  • Wall-mounted in the heated room or positioned elsewhere in the property — fully flexible siting
  • Suitable for domestic and commercial buildings
  • Compatible with all Polypipe UFH systems: Overlay™, Overlay™ Lite, MHP, solid screeded floors, and more
Zonal Regulation Unit body (pump, blending valve, pipe stat)
2-circuit built-in manifold (flow & return)
Wiring module with terminal block
Wall fixing template & screws
Fixing plugs
Installation guide
ℹ️ 3rd circuit upgrade: To form a third heating circuit, add 2 × 15mm spigot elbows and 2 × 15mm tees to the ZRU manifold ports. These standard Polypipe PolyPlumb fittings are sold separately.

The ZRU forms a low-loss header between the existing heating circuit and the UFH loops, managing temperature and flow automatically. The six-step operational sequence is:

  1. Boiler fires: Heating water circulates from the boiler through the existing system pipework and enters the ZRU via the Heating Flow connection.
  2. Pipe thermostat activates: The built-in pipe thermostat senses that heating water is available (≥45°C) and sends a live signal to the ZRU pump.
  3. Room thermostat calls for heat: If a room thermostat is fitted and the room temperature is below setpoint, the pump starts and draws water into the UFH circuits.
  4. Thermostatic blending valve regulates temperature: A mixture of hot flow water and cooler UFH return water is blended to the correct underfloor temperature (adjustable 30–60°C) before being pumped into the loops.
  5. Room thermostat satisfied: When the room reaches setpoint, the thermostat breaks the signal to the pump — the UFH pump stops, but the existing heating system continues to run normally.
  6. Boiler shuts down: As the boiler switches off and main flow water cools below 45°C, the pipe thermostat breaks the pump signal and the ZRU goes to standby.
MPN / Product Code PB970028
Manufacturer Polypipe
Product Type Zonal Regulation Unit (ZRU) — 2/3 Circuit, complete with manifold
Max Room / Extension Area Up to 30 m²
Number of UFH Circuits 2 (built-in manifold); expandable to 3 with standard 15mm fittings
Flow Temperature Control Thermostatic blending valve — adjustable 30°C to 60°C
Minimum Boiler Water Temperature to Activate 45°C (pipe thermostat make point)
Pipe Thermostat: Make / Break Makes at 40°C / Breaks at 32°C
Electrical Supply 240V AC, 3A fused spur
Room Thermostat Connection Volt-free contact (battery-operated or wired thermostat); remove link on wiring block when thermostat fitted
Pipework Connections 15mm compression — Heating Flow, Heating Return, UFH Flow(s), UFH Return(s)
Minimum Pipe Size to ZRU 15mm (do not connect from any pipe smaller than 15mm)
Preferred System Connection Main 22mm flow and return distribution pipework of a 2-pipe system
Pressure Rating PN6
Max Ambient Temperature 60°C (at 95°C fluid temperature)
Mounting Wall-mounted — 100mm minimum from finished floor level
Mounting Clearance 80mm minimum wall clearance for mixing valve adjustment access
Application Domestic and commercial — all Polypipe UFH floor types
Compatible UFH Systems: Polypipe Overlay™ · Overlay™ Lite · MHP (Minimum Depth) · Solid screeded floor systems · Low surface temperature (LST) radiator applications
⚠️ Competent person required: All electrical connections must comply with the current edition of BS 7671 (IET Wiring Regulations). Electrical work must be carried out by, or inspected and tested by, a qualified electrician. Plumbing connections must comply with the Water Supply (Water Fittings) Regulations 1999. Always check boiler manufacturer guidance before installing a second pump on the system.
  1. Pre-fill UFH pipework: If the ZRU is to be installed after floor screed or coverings are laid, fill and pressure-test the UFH circuit beforehand. Temporarily cap the pipes and keep them full of water (under pressure where possible). Take precautions against freezing in cold conditions.
  2. Select mounting position: Ideally mount in the heated room at 100mm above finished floor level to allow pipe connections to exit the floor correctly. The ZRU can alternatively be positioned elsewhere in the property if more convenient. Ensure 80mm minimum clearance to the left of the unit for mixing valve access.
  3. Fix to wall (Step 1): Tape the supplied fixing template to the wall. Mark and drill fixing holes. Insert wall plugs and screw the ZRU body firmly to the wall. Do not over-tighten fixings.
  4. Connect heating pipework (Step 2): Connect the Heating Flow and Heating Return ports to the existing 2-pipe system via isolation valves. The preferred connection point is the main 22mm distribution pipework. Alternatively connect to the nearest existing radiator. Do not connect from any pipe smaller than 15mm.
  5. Connect UFH circuits (Step 3): Connect the underfloor heating flow and return loops to the ZRU manifold ports using isolation valves. For 2 circuits, use the built-in manifold ports. To add a 3rd circuit, fit 15mm spigot elbows to the underside exit points and use 15mm tees off the manifold. Blank off any unused ports with spigot blanking plugs. Use PolyPlumb elbow fittings to exit pipes from floor level; cover elbows in polystyrene before screeding to allow future access, or enclose within a PolyPlumb Junction Box.
  6. Wire electrical connections (Step 4): Connect 240V mains supply via a 3A fused spur to the ZRU wiring block as per the wiring diagram in the installation guide. If a room thermostat is being fitted, connect the volt-free contacts to the designated terminals and remove the shorting link from the wiring block. If no thermostat is fitted, leave the link in place — the ZRU will run purely on pipe thermostat control.
  7. Fill and commission: Fill the complete system (boiler, radiators, and UFH circuits) and bleed any air. Check all connections for leaks. Set the thermostatic blending valve to the desired UFH flow temperature (typically 35–50°C depending on floor construction). Fire the boiler and confirm the ZRU pump starts when flow temperature exceeds 45°C. Verify correct operation of the room thermostat (if fitted).
ℹ️ Solid floor timing note: For solid screeded floor installations, the thermal mass of the floor means slow response times. The timings of the existing central heating may need adjusting so the UFH circuit has sufficient warm-up time before occupancy. Low-mass systems (Overlay™, Overlay™ Lite, MHP) respond much faster and are generally compatible with existing boiler on/off timing.
💡 Independent zone operation: To operate the UFH room completely independently of the existing heating system (e.g. different schedule or setpoint), install a zone valve between the boiler/distribution pipework and the ZRU Heating Flow connection, controlled by a programmable room thermostat. Without this, the ZRU will only operate when the existing heating system is also running.
Can I add underfloor heating to just one room without changing my existing radiator system?
Yes — that is exactly what the ZRU is designed for. It connects a single room or extension to your existing radiator circuit without any modifications to the boiler, pump, or existing pipework. It has its own pump and mixing valve and manages the temperature conversion internally.
My existing system runs at around 75°C. Is that too hot for UFH?
Not with the ZRU. The built-in thermostatic blending valve reduces the flow temperature to between 30°C and 60°C before it reaches the UFH pipework. You set the blending valve to the appropriate temperature for your floor construction — typically 35–45°C for a screed floor and up to 50°C for a timber floor system.
Does the ZRU work if my boiler is a combi?
Yes, the ZRU is compatible with combi boilers. However, note that adding a second pump to the system can affect some boilers hydraulically — always check with the boiler manufacturer that a second pump is compatible before installation.
What happens if my boiler is off? Will the underfloor heating still work?
No — the ZRU only operates when the boiler is supplying heat. The pipe thermostat within the unit detects when flow water reaches 45°C and only then starts the UFH pump. If the boiler is off, the ZRU pump will not run. To allow the UFH to run independently on a separate schedule, a zone valve is needed (see installation note above).
How many circuits can the ZRU serve?
The PB970028 includes a built-in 2-circuit manifold, so it can serve two UFH loops directly out of the box. A third circuit can be added by fitting two 15mm spigot elbows and two 15mm tees to the manifold — standard PolyPlumb fittings available separately. For rooms over 30 m², Polypipe recommend connecting via a full multi-circuit manifold rather than a ZRU.
Do I need a room thermostat?
A room thermostat is optional. Without one, the ZRU operates purely on the pipe thermostat — running whenever the boiler is on and stopping when the boiler shuts down. Adding a volt-free room thermostat (battery-operated or wired) allows the room temperature to be set and maintained precisely, stopping the UFH pump once the room reaches temperature even if the boiler is still running. This is strongly recommended for energy efficiency and comfort.
Where should the ZRU be mounted?
Ideally on the wall of the room being heated, at 100mm above the finished floor level so that the UFH pipe connections exit from the floor cleanly beneath it. If this is not practical, it can be positioned elsewhere in the property — for example in a hallway cupboard — as long as the pipe stat will still accurately detect the system flow temperature.
What pipe size is required to connect the ZRU?
All connections to the ZRU are 15mm compression. The ZRU must not be connected to the existing system from a pipe smaller than 15mm. The preferred connection point is the main 22mm flow and return distribution pipework; the system can also be connected from the nearest radiator if more convenient.
Can the ZRU be used for low surface temperature (LST) radiators instead of UFH?
Yes. Because the ZRU thermostatically controls water temperature, it can also be used to supply low surface temperature radiators where the maximum surface temperature must be limited — for example in schools, care homes, or healthcare settings.
What floor types is the ZRU compatible with?
The ZRU is compatible with all Polypipe wet UFH systems: screeded solid floor systems, Overlay™ low-profile board systems, Overlay™ Lite, and MHP (Minimum Depth Panel) systems. For low-mass systems (Overlay™, Overlay™ Lite, MHP), the fast response means the ZRU works well with the existing boiler's on/off timer. For solid screeded floors, you may need to advance the existing heating start time to allow the floor mass to warm up in time.